AUTOMATIC TRANSFER SWITCH
LEXX0526-03
FEATURES
ELECTRICAL RATINGS
Ratings 100 to 4000 amperes
2, 3 or 4 Poles
NEMA 1, 3R, 4, 4X and 12
Available with CTS, CTSD and CTSCT Series
Transfer Switch
Bypass and transfer switch have identical ratings
Suitable for emergency and standby applications
on all classes of load, 100% tungsten rated through
400 amps
UL 1008 listed at 480 VAC
CSA C22.2 No. 178 certified at 600 VAC
IEC 947-6-1 listed at 480 VAC
PERFORMANCE FEATURES
Load is not interrupted during bypass operation
High close-in and withstand capability
Temperature rise test per UL 1008 conducted after
overload and endurance tests in unventilated
enclosure – exceeds UL requirements
DESIGN AND CONSTRUCTION FEATURES
Transfer switch is located on a draw out mechanism to
facilitate maintenance
Emergency power systems can be electrically tested
without disturbing the load
Power cables do not have to be disconnected to
remove transfer switch
Bypass to any available source with transfer
switch removed
Engine start circuit maintained during bypass
operation; normal power failure causes engine
start contact closure even with the ATS removed
Diagnostic lights and detailed instructions for
simple step by step operation
Mechanical and electrical interlocks ensure proper
sequence of operation
Bypass switch contacts are closed only during the
bypass-isolation operation
Silverplated copper bus interconnection of the
transfer and bypass switches on all sizes
Transfer/Bypass-Isolation Switches
The automatic transfer switch is a key element in
any emergency power system. The importance
of the transfer switch increases as the need for
dependable power grows. Though designed to
give consistent operation, the automatic transfer
switch must be periodically maintained to
ensure proper operation and system reliability.
Maintenance of the entire system is called for in
the National Electrical Code Article 700-4, NEMA
Standard ICS2-447 and in NFPA 99.
CBTS SERIES –
SUPPLEMENT
OPEN TRANSITION
BYPASS SWITCH
Page view 0
1 2 3 4 5

Summary of Contents

Page 1 - BYPASS SWITCH

AUTOMATIC TRANSFER SWITCH LEXX0526-03 FEATURES ELECTR

Page 2 - AUTOMATIC TRANSFER SWITCH

AUTOMATIC TRANSFER SWITCH LEXX0526-03 2 In some non-critical emergency power systems, it is possible to disconnect the power feeders from the aut

Page 3

AUTOMATIC TRANSFER SWITCH LEXX0526-03 3 Interlocks and Indicators Every CBTS Series Bypass-Isolation Transfer Switch is supplied with all necessa

Page 4

AUTOMATIC TRANSFER SWITCH LEXX0526-03 4 DIMENSIONAL SPECIFICATIONS Ampere Height Width Depth Reference ApplicationRating Poles (A) (B) (C) Fig

Page 5

AUTOMATIC TRANSFER SWITCH LEXX0526-03 5 DIMENSIONAL SPECIFICATIONSAmpere Height Width Depth Reference ApplicationRating Poles (A) (B) (C) Figure